·YJLHV 8030 series aluminum alloy cable
-YJLHV is a high flexibility aluminum alloy type 90℃ crosslinked polyethylene insulatedsingle core or multi-core aluminum alloy cable.
-WDZA-YJLHV type flame retardant grade A aluminum alloy cable can also beproduced according to customer requirements.
·Product standard
1.GB/T12706-2008 rated voltage lkV(Um=1.2KV)to 35KV(Um=40.5KV)extruded insulatedpower cable and accessories
2.GB/T19666-2005 flame retardant and fire-resistant wire and cable general rules
3.Q/320282 DDF029-2012 cable with 8000 series aluminum alloy conductor
4.GB/T 31840-2015rated voltage 1KV(Um=1.2KV)to 35KV(Um=40.5KV)extrudedinsulated aluminum alloy core power cable
·Product features
1.The 8030 series aluminum alloy conductor developed by ourselves has the characteristicsof high conductivity,good resistance to wax degeneration,high flexibility,highextension,low rebound and stable connection,and its performance exceeds theperformance requirements of ASTMB800-05 standard.
2.The high strength 5000 series aluminum alloy is strong and tough,with good bending andexcellent shielding performance;
3.Cable does not contain heavy metal elements,green environmental protection,flameretardant performance reaches halogen-free low smoke flame retardant class A.
4.The cable can be located indoors,directly buried in the wall and in the dry environmentof the tunnel,light weight,saving the cost of installing the bridge,etc.,and has a numberof pipeline modes
5.Set the same perfomance.
Technical parameters table
·Table 1, YJLHV YJLHY-1 ~3kv aluminum alloy cable physical parameters table
| Nominal section (mm²) |
Approximate outer diameter of cable (mm) | Approximate cable weight (kg/km) | ||||||||||||
| 2 Cores |
3 Cores |
4 Cores |
3+1 Cores |
5 Cores |
4+1 Cores |
3+2 Cores |
2 Cores |
3 Cores |
4 Cores |
3+1 Cores |
5 Cores |
4+1 Cores |
3+2 Cores |
|
| 10 | 17.6 | 20.5 | 21.9 | 21.3 | 23.4 | 23.0 | 22.4 | 132 | 174 | 220 | 203.1 | 272 | 253 | 237 |
| 16 | 19.7 | 22.7 | 24.3 | 23.7 | 26.1 | 25.8 | 25.2 | 180 | 242 | 307 | 285 | 359 | 359 | 337 |
| 25 | 21.7 | 26.1 | 28.2 | 27.3 | 30.4 | 29.8 | 28.9 | 260 | 355 | 454 | 418 | 529 | 529 | 489 |
| 35 | 24.9 | 28.3 | 30.3 | 29.1 | 33.1 | 32.0 | 30.6 | 331 | 457 | 587 | 517 | 661 | 661 | 595 |
| 50 | 26.9 | 31.5 | 33.1 | 32.8 | 36.1 | 35.0 | 33.7 | 445 | 621 | 804 | 717 | 916 | 916 | 826 |
| 70 | 29.39 | 34.3 | 37.5 | 35.5 | 40.9 | 39.5 | 37.7 | 582 | 819 | 1063 | 944 | 1218 | 1218 | 1094 |
| 95 | 33.5 | 37.3 | 40.8 | 39.0 | 44.7 | 43.4 | 41.6 | 741 | 1051 | 1369 | 1228 | 1582 | 1582 | 1430 |
| 120 | 35.2 | 41.0 | 44.9 | 43.2 | 49.3 | 48.1 | 46.4 | 917 | 1309 | 1709 | 1548 | 1984 | 1984 | 1817 |
| 150 | 38.6 | 44.6 | 49.0 | 46.2 | 53.9 | 51.8 | 49.2 | 1117 | 1601 | 2094 | 1837 | 2382 | 2382 | 2118 |
| 185 | 42.0 | 49.6 | 54.6 | 51.3 | 64.3 | 57.6 | 54.5 | 1367 | 1967 | 2577 | 2276 | 2946 | 2946 | 2642 |
| 240 | 46.6 | 55.0 | 64.8 | 56.8 | 71.1 | 68.2 | 64.6 | 1724 | 2491 | 3422 | 2880 | 3893 | 3893 | 3493 |
| 300 | 516 | 63.9 | 70.1 | 66.0 | 77.0 | 73.9 | 70.1 | 2099 | 3195 | 4170 | 3682 | 4750 | 4750 | 4264 |
| 400 | 56.0 | 71.2 | 78.3 | 73.6 | 86.2 | 82.6 | 78.2 | 2892 | 4152 | 5434 | 4755 | 6131 | 6131 | 5454 |
| 500 | 67.0 | 78.8 | 86.8 | 81.5 | 95.6 | 91.6 | 86.6 | 3558 | 5128 | 6723 | 5899 | 7589 | 7589 | 6768 |
| 630 | 74.0 | 87.6 | 87.6 | 90.2 | 106.7 | 101.7 | 95.7 | 4408 | 6375 | 8370 | 7322 | 9415 | 9415 | 8370 |
·Table 2. YJLHV YJLHY-1 ~3kV aluminum alloy cable current carrying meter
| Nominal section |
Approximate outer diameter of conductor |
Nominal insulation thickness lkv |
1.8/3 nominal insulation thickness |
DC resistance at 20℃ |
Carrying capacity | |||
| 2 Cores | 3~5 Cores | |||||||
| mm2 | mm | mm | mm | ≤2/km | A | A | A | A |
| 10 | 3.80 | 0.7 | 2.0 | 3.08 | 67 | 83 | 57 | 70 |
| 16 | 4.80 | 0.7 | 2.0 | 191 | 86 | 106 | 75 | 91 |
| 25 | 6.00 | 0.9 | 2.0 | 1.21 | 114 | 138 | 100 | 117 |
| 35 | 6.60 | 0.9 | 2.0 | 0.868 | 137 | 165 | 120 | 138 |
| 50 | 7.70 | 1.0 | 2.0 | 0.641 | 171 | 197 | 149 | 170 |
| 70 | 9.22 | 1.1 | 2.0 | 0.443 | 217 | 239 | 189 | 207 |
| 95 | 10.90 | 1.1 | 2.0 | 0.320 | 268 | 292 | 234 | 250 |
| 120 | 12.30 | 1.2 | 2.0 | 0.253 | 314 | 334 | 274 | 281 |
| 150 | 13.50 | 1.4 | 2.0 | 0.206 | 360 | 371 | 308 | 318 |
| 185 | 15.30 | 1.6 | 2.0 | 0.164 | 417 | 419 | 360 | 361 |
| 240 | 17.40 | 1.7 | 2.0 | 0.125 | 496 | 499 | 428 | 419 |
| 300 | 19.50 | 1.8 | 2.0 | 0.100 | 582 | 581 | 496 | 472 |
| 400 | 22.00 | 2.0 | 2.0 | 0.0778 | 673 | 663 | 582 | 541 |
| 500 | 26.00 | 2.2 | 2.0 | 0.0605 | 781 | 764 | 702 | 626 |
| 630 | 30.20 | 2.4 | 2.0 | 0.0469 | 930 | 901 | 833 | 711 |
| Ambient temperature/Buried depth 0.7m | 30℃ | 20℃ | 30℃ | 20℃ | ||||
| Maximum operating temperature of conductor | 90℃ | |||||||
Language