- Reference Standards
The product is manufactured according to the standard of GB12706-2020 or IEC, BS, DIN and ICEA upon request.
- Applications
The product is suitable for use in power transmission and distribution lines with rated power frequency voltage 26/35kv.
- Operating characteristics
-- XLPE Insulated Electrical Cable for rated power frequency voltage Uo/U:3.6/6kV-26/35kV
· Max. permissible continuous operating temperature of conductor:90°C.
· Max. short-circuit temperature of conductor shall not exceed 250°C.
· The ambient temperature under installation shall not below O°C.
· The bending radius of single-core cable shall not less than 20 times of the cable diameter.
-- XL.PE Insulated Electrical Cable for rated power frequency voltage Uo/U:0.6/kV.
· Max. permissible continuous operating temperature of conductor:90°C.
· Max. short-circuit temperature of the conductor shall not exceed 250℃ (5s maximum duration).
· The ambient temperature under installation shall not below O°C.
· The bending radius of a cable shall not less than 15 times of the cable diameter.
-- XL.PE Insulated Electrical Cable for rated power frequency voltage Uo/U:0.6/1kV.
·Max. permissible continuous operating temperature of conductor:70°C
·Max. short-eircuit temperature of the conductor shall not exceed 160°C.
·(5s maximum duration)
· The ambient temperature under installation shall not below O°C.
·The bending radius of a cable shall not be less than 15 times of the cable diameter.
- Voltage designation
The rated voltage of the cable for a given application s hall be suitable for the operating conditions in the system in which the cable is used, and is expressed in the form of Uou (tn)kV Where:
· Uo-: The rated power-frequency voltage between conductor and screen or metallic- sheath, for which the cable designed;
· U-: The rated power-frequency voltage between conductors, for which the cable designed;
· Um-: The maximum value of the “highest system voltage" for which the equipment may be operated.
The Uo values of cables for three-phase system are recommended as follows:
|
U |
Um |
Uo |
|
|
First class |
Second class |
||
|
1 |
1.2 |
0.6 |
0.6 |
|
3 |
3.6 |
1.8 |
3.6 |
|
6 |
7.2 |
3.6 |
6 |
|
10 |
12 |
6 |
8.7 |
|
15 |
17.5 |
8.7 |
12 |
|
20 |
24 |
12 |
18 |
|
35 |
42 |
21 |
26 |
The first type is used for single-phase grounding fault time not more than 1 min at a time, and it can also be used for systems with a maximum time of no more than 8h and a cumulative annual total of no more than 12h. The second type is used in the system with longer grounding fault time and the occasions with higher requirements for cable insulation performance.